Homeowner Hint #10

Why Is One of My Radiators Not Working?

You would be amazed how many times I’ve been paid to visit somebody’s house and simply turn a radiator on.

British Gas taught me to start with the easiest and cheapest thing to fix first. Do the same here before assuming you need new valves, a power flush or a bigger repair.

Start With the Obvious: Is It Turned On?

Make sure both radiator valves are open. Somebody may have turned the radiator off and forgotten about it. If opening the valve makes it heat straight away, there was nothing else wrong.

Thermostatic radiator valves are also notorious for sticking after summer. A normal TRV does not communicate with the boiler: it reacts to the temperature of the air around it. The wax inside expands as the room warms and pushes a small pin down to close the valve.

The numbers do not change the radiator-water temperature. A radiator can feel just as hot on setting 2 as setting 5. The lower setting simply makes the valve shut at a lower room temperature.

Check the TRV Pin

During warm weather the wax remains expanded and the pin can sit closed for weeks. When the heating comes back on, that little pin sometimes stays stuck down.

1. Remove the headRemove only the plastic thermostatic head so you can see the small metal pin beneath it.
2. Test the pinGently press it. It should move down slightly and spring back up again.
3. Free it gentlyIf it is stuck down, light tapping around it can often free it. Gentle means gentle—do not pull the pin out.

You are removing the plastic head, not undoing the metal valve body from the pipework. Stop if the pin will not free or any water appears.

Upstairs or Downstairs Makes a Difference

Highest Radiator Is Cold

Air rises, so a cold radiator on the top floor or in a loft conversion may contain air. Check the system pressure as well. A boiler downstairs may still run at 0.6 bar while only about 0.1 bar remains at the top of a tall house—not enough to fill that radiator properly.

Ground-Floor Radiator Is Cold

In a typical house, a completely cold lounge radiator downstairs is unlikely to be full of air while the upstairs radiators work normally. Start thinking about valves, flow, balancing or sludge.

Feel Both Radiator Pipes

Once the valves are open and the TRV pin moves, feel the two pipes connected to the radiator. Their temperatures tell you what is happening.

Both Pipes Cold

No flow is reaching the radiator.

One Hot, One Cold

Heat is arriving, but the flow through the radiator is poor or restricted.

Both Pipes Warm, Radiator Cold

The radiator itself is likely to be badly restricted with sludge.

Force the Water Through the Cold Radiator

Water always takes the easiest route. Leave the heating running, keep the problem radiator open and temporarily turn every other radiator off. This removes the easy routes and forces the pump towards the cold one.

If it now gets hot: the radiator can work and the system is probably badly balanced. If it stays cold: a valve is not opening or there is a serious blockage in the radiator or its pipework.

Remember to reopen the other radiators after the test.

What Does Balancing Actually Do?

A modern boiler responds to the temperature of the water returning to it. If hot water takes the easy route through radiators close to the boiler or pump and comes back hot, the boiler can modulate down even though a distant radiator is still freezing.

Balancing restricts those easy routes and encourages water to travel where it is needed. I start nearest the boiler or pump with the lockshield only slightly open, then work away from the heat source and allow progressively more flow. The furthest or problem radiator is left open the most.

A complete balancing job means adjusting several lockshield valves in small increments and retesting the whole system. If the forced-flow test proves the radiator works but you are not confident balancing it, that is the point to call.

When the System May Need Cleaning

Cold areas across the bottoms of radiators, poor flow through several radiators, dirty system water or a boiler repeatedly firing and stopping without properly warming the house can point towards contamination and restricted circulation.

Bleeding will not remove sludge. At that stage it is worth considering proper system cleaning or power flushing.

Read about power flushing and system cleaning →

You’ve Done the Basics—Know When to Stop

You may have saved yourself paying for a pointless call-out by checking the valve position, TRV pin, pressure, air and forced flow. But stop and call a heating engineer if:

  • The TRV pin will not free
  • Water appears around a valve
  • The radiator stays cold with every other radiator turned off
  • The boiler pressure keeps dropping after bleeding
  • Several radiators have cold bottoms or poor flow
  • The boiler repeatedly fires and stops without heating the house
Do not keep wasting money trying to heat a house that cannot heat properly. Once the sensible checks fail, the valve, radiator or pipework needs testing and the actual fault needs repairing.
Radiator Problems in Bromley?

Tell Me What the Checks Showed

Call or WhatsApp me and tell me whether the radiator is upstairs or downstairs, which pipes get warm, whether it heats when the other radiators are turned off and what the boiler pressure is showing. Those answers can narrow the problem down before I arrive.